Agilent Technologies HP 70903A IF SECTION Manual de servicio Pagina 26

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 25
Adbess Switches
Installation 2-3
J
ROW 2, COLUMN 18 ,
Figure 2-l.
Module
1
B
I
SWITCH SET T O
=
0= OF F
HP-MS
-l= ON
=
Setting the HP-MSIB Address Switches
A
module-address change requires the following steps:
1. Locate the address switches on the right side-panel of the module. See Figure 2-l for
an example of the switches.
2. Set the address switches labeled rowto the binary value of the module s HP-MSIB
row number. For example, if the row value is 2, set the switches to binary 010 as
shown in Figure 2-l.
3. Set the five switches labeled column to the binary value of the module s HP-MSIB
column number. For example, if the column value is 18, set the switches to binary
10010 as shown in Figure 2-l.
Note
3
Changing HP-MSIB addresses requires an
understanding
of
HP-MSIB
addressing rules. For information on determining and assigning HP-MSIB
addresses, refer to the installation and verification manual for the system
master (for example, HP 70900A Local Oscillator).
ROW
ADDRES S
MODULE ADDRES S
Vista de pagina 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 43 44

Comentarios a estos manuales

Sin comentarios