Agilent Technologies DP111 Especificaciones Pagina 217

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 452
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 216
Section 5 Maintenance S100 I/O Interface – CI856
3BSE036351-510 A 217
S100 I/O Interface – CI856
Table 36. S100 I/O CI856 – Fault Finding
Fault Possible Cause and Corrective Action
Neither R(un) nor F(ault)
LED’s are ON
The CI856 unit is in the process of being
configured. Allow time for this to finalize.
If the condition persists, and no other unit LED on
the CEX-Bus is lit:
Check that a valid HW configuration including
the CI856 is downloaded to the controller.
Check the CEX-Bus fuse inside the PM8xx
processor unit
Initiate a reset signal (INIT) from the PM8xx
processor unit
Replace the CI856 unit
F(ault) LED is ON The CI856 unit is in the process of being
restarted. Allow time for this to finalize.
Replace unit if the condition persists.
CI856 supports hot swap.
Vista de pagina 216
1 2 ... 212 213 214 215 216 217 218 219 220 221 222 ... 451 452

Comentarios a estos manuales

Sin comentarios