Agilent Technologies DP111 Especificaciones Pagina 290

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 452
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 289
CI852 and TP852 – FOUNDATION Fieldbus H1 Interface Appendix A Hardware Units
290 3BSE036351-510 A
Indicators
The CI852 FOUNDATION Fieldbus H1 interface has the following LED indicators.
Technical Data
Table 78. CI852 FOUNDATION Fieldbus H1 – LED Indications
Indication/Color Function
F(ault) /Red Unit error detected. Controlled by Control
Software. Set and cleared by the Hardware during
controller Reset.
R(un) /Green Operating. Controlled by the Control Software.
Cleared by the Hardware during controller Reset.
Rx/Tx /Yellow Transmission to or from the unit.
Table 79. CI852 FOUNDATION Fieldbus H1 Interface Specifications
Item Description
Type – FOUNDATION Fieldbus H1 master and link
schedule.
– Note the complete controller has a HW
capability necessary for a FOUNDATION Fieldbus
linking device.
Number of channels Single channel FOUNDATION Fieldbus H1
(31.25 kbit/s).
Protocols FOUNDATION Fieldbus H1 via port on CI852.
Communication speed 31.25 kbit/s (FF H1)
Allowed node address 20 – 247
Galvanic isolation By means of transformer.
Vista de pagina 289
1 2 ... 285 286 287 288 289 290 291 292 293 294 295 ... 451 452

Comentarios a estos manuales

Sin comentarios